P+F Engineering Process Fieldbus Installations

The fieldbus infrastructure constitutes the backbone of your automation system. Design rules apply analogous to any electrical installation. The following engineering criteria are important for reliability and cost-effectiveness:

 

  • Choices such as redundancy or protection from short-circuits, power surges, or water ingress
  •  Methods of ignition protection typical for fieldbus installations in Zones and Divisions 

 

Topology and components—simplicity for engineering and handling

A segment is a single circuit with power supply, fieldbus junction boxes, and instruments. The segment connects the control system to multiple instruments. The topology design determines the physical location and connection of power supplies, fieldbus junction boxes, and instruments.

The typical topology for a segment is the trunk-and-spur topology with a main line or master cable (trunk). The trunk connects the power supplies and communication interfaces located in the control room with the field. One or more fieldbus junction boxes mounted where they are easily accessible provides connections for field devices. The connection cable with a length of up to 120 m is called a spur, as it is typically much shorter in comparison to the trunk. This topology fits practically all process plants.

With its many similarities to the topologies known from multi-core trunk cables leading to a fieldbus junction box installed in the field, the trunk-and-spur? topology is easy to understand, engineer, and maintain.

 


Trunk-and-spur topology provides simplicity by design. Each device is connected separay.

The fieldbus junction box is also called the device coupler. Where it is required, ignition protection is scalable through a selection of power supplies and device couplers. This enables economic solutions for any hazardous area.

 

Download Segment Checker—the easy to use segment design tool

Download and install the free software tool to easily design and layout your fieldbus segments as well as engineer cable lengths based on the devices you use. Device libraries let you choose the instruments of your favorite manufacturer. Make fieldbus installation a simple click process …

 

Function and availability

Modern-day device couplers provide reliable protection from typical working conditions such as device exchange, contact bounce, water ingress or power surges, etc. These functions are described in detail here …

FieldConnex simplifies engineering and implementation of fieldbus installations for any process plant in any industry with selections and options for protection from ambient conditions, and for the right availability.

See all fieldbus components for use in non-explosion hazardous areas and find the right components for your plant here …

 

 

Fieldbus in hazardous areas

Fieldbus in hazardous areas requires an infrastructure with ignition protection. See below the topology for any hazardous area: Read the details on methods of ignition protection here …

 


Identical topology with trunk and spurs for any hazardous area. Selecting the components and installation methods provides ignition protection.

會員登錄

×

請輸入賬號

請輸入密碼

=

請輸驗證碼

收藏該商鋪

X
該信息已收藏!
標簽:
保存成功

(空格分隔,最多3個,單個標簽最多10個字符)

常用:

提示

X
您的留言已提交成功!我們將在第一時間回復您~

以上信息由企業自行提供,信息內容的真實性、準確性和合法性由相關企業負責,化工儀器網對此不承擔任何保證責任。

溫馨提示:為規避購買風險,建議您在購買產品前務必確認供應商資質及產品質量。

撥打電話
在線留言